Release 0.4.0
Zones, electrical heat sources, windows with ventilation, wind exposure
and recovery, and exchange between adjacent zones, all observational.
docs/MODEL.md documents the equations, units, coefficient meanings,
priors and bounds, learning conditions, forecast assumptions, validation
method and results, and limitations. README gains a configuration guide
for zones, heat sources and windows, the new diagnostics and the
accuracy comparison against the base model. CHANGELOG has upgrade notes
(config entry version 3, rollback needs the backup, renamed Status
attributes). ROADMAP marks the Milestone 2 items now covered; AUDIT
records the design decisions and evidence. AGENTS.md lists the new
modules and the convention that new model terms start at zero and must
beat the base model out of sample before being relied on.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-27 03:02:21 +02:00

219 lines
11 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Heating MPC thermal model
This document describes the model used from version 0.4.0: what it computes, the
units and meaning of every coefficient, when each part learns, what the forecasts
assume, and how the model is validated. It is observational: nothing here controls
the boiler.
## Time step and inputs
The model works in 5-minute steps, the polling interval. For each zone *i*, each
poll provides:
| Symbol | Meaning | Unit | Source |
|---|---|---|---|
| T_i | Zone temperature: sensor-weighted mean of its usable sensors | °C | zone sensors |
| T_out | Outdoor temperature (first fresh, valid source) | °C | weather sources |
| lag | Radiator-lag proxy, 0 (cold) to 1 (fully warm); 20-minute first-order response to the relay, integrated at the relay's actual switch times | – | relay state + read-only listener |
| q_i | Electrical heat above baseline after its thermal response | kW | heat sources |
| O_i | Sum of open windows' opening factors, weighted by the share of the interval they were open | – | window sensors |
| F_i | Same, each window also weighted by cos(angle between wind direction and the window's facing) | – | windows + wind direction |
| v, g | Wind speed and gust speed | m/s | weather sources |
| R_i | Recovery weight after the zone's last window closed: exp(−t / τ_rec), 0 below 0.05 | – | window sensors |
| T_ref,i | Zone temperature at the poll before the window opened | °C | zone sensors |
## Equations
Per 5-minute step, the predicted change of zone *i* is the sum of layers:
```text
ΔT_i = loss × (T_out − T_i) envelope heat loss
+ heat × lag boiler, through the radiators
+ bias constant gains and losses
+ internal × q_i electrical heat above baseline (extended layer)
+ Σ_j couple:j × (T_j − T_i) exchange with adjacent zones (extended layer)
+ vent_natural × O_i (T_out − T_i) (ventilation layer)
+ vent_wind × O_i v (T_out − T_i)
+ vent_wind_dir × F_i v (T_out − T_i)
+ vent_gust × O_i max(0, g − v) (T_out − T_i) (optional)
+ vent_cross × O_i O_other (T_out − T_i) (optional)
+ recovery × R_i (T_ref,i − T_i)
```
All coefficients are in °C per 5 minutes per unit of their term. They are
statistical estimates, not measured physical properties: `heat` is not boiler
efficiency, and a relay that is on does not prove the burner is firing.
In conceptual continuous-time form this corresponds to
```text
C_i dT_i/dt = UA_i (T_out − T_i) + Q_boiler + Q_internal + Q_ventilation + Σ_j K_ij (T_j − T_i) + Q_other
```
divided through by the zone's effective heat capacity C_i and discretized to 5
minutes. The model is first-order (one temperature per zone). Thermal inertia
enters through the radiator lag, the electrical response filter and the recovery
term; a separate wall-mass state is not modeled (see Limitations).
### Base layer
The base layer is the 3-parameter model of earlier versions (loss, heat, bias),
learned per zone. It is always kept: it is the fallback whenever another layer's
inputs are unknown, and the comparison that shows whether the other layers help.
### Extended layer
Present when a zone has an enabled heat source or an adjacent zone. It learns all
base terms plus `internal` and `couple:<zone>` and replaces the base layer in
forecasts once it is as trained as the base layer needs to be (200 samples, 30 with
the relay on, 30 off). If any of its inputs is unknown, the base layer is used.
### Electrical heat
For each enabled source:
```text
effective power = measured W − measured W of enabled sources included in it (≥ 0)
baseline = 20th percentile of the last 24 h of effective power, or the manual value
variable heat = heat fraction × (effective power − baseline) / 1000 (kW)
thermal response : r ← r + (1 − exp(−5 min / τ)) × (variable heat held during the interval − r)
```
q_i is the sum of the responses of the zone's sources. Centring on the baseline
matters: the persistent load (for example a UPS drawing 200 W all day) is already
part of the bias term, so feeding it again would count it twice. The baseline
needs one hour of data; after startup or an outage a source's response must run
for two time constants before it is used for learning.
Only active power counts (W, kW, mW). VA (apparent power) and % (UPS load) are
rejected. A UPS output sensor does not include the UPS's own losses; if they matter,
measure the input side or lower the heat fraction accordingly.
### Ventilation layer
Present when a zone has an enabled window. Learned separately, from the part of
the measured change the closed-window layers cannot explain, only while a window is
open, its state is unknown, or the zone is recovering. During those periods the
base and extended layers do **not** learn, so window events cannot inflate `loss`
or shift `bias`.
`vent_wind_dir` is bounded by `vent_wind` (|vent_wind_dir| ≤ vent_wind), so the
combined wind term never goes negative: a leeward window still ventilates.
Wind direction is meteorological: the direction the wind comes **from**, degrees
clockwise from north. A window's azimuth is the direction its outside faces. Wind
from the azimuth blows straight at the window (cos = 1); wind from behind the
building gives −1. Angle differences wrap around north correctly.
## Priors, bounds and confidence
| Coefficient | Prior | Bounds | Prior worth |
|---|---|---|---|
| loss | 0.002 | 0 … 0.04 | as in earlier versions |
| heat | 0.045 | 0 … 0.25 | as in earlier versions |
| bias | 0 | −0.06 … 0.06 | as in earlier versions |
| internal | 0 | 0 … 0.5 | 20 samples at 0.4 kW |
| couple:j | 0 | 0 … 0.05 | 200 samples at 1 °C difference |
| vent_natural | 0 | 0 … 0.2 | 20 samples at opening 1, 15 °C difference |
| vent_wind, vent_wind_dir | 0 | 0 … 0.03 / ±vent_wind | 20 samples at 4 m/s |
| vent_gust | 0 | 0 … 0.03 | 20 samples |
| vent_cross | 0 | 0 … 0.1 | 100 samples |
| recovery | 0 | 0 … 0.5 | 20 samples at 0.5 °C deficit |
New effects start at 0: no effect is assumed until the data shows one. Learning is
recursive least squares with exponential forgetting (about 3.5 days of samples),
a covariance bound that stops windup during long periods without excitation, and
outlier rejection above 0.8 °C per 5 minutes.
Each coefficient reports:
* `confidence`: the share of its information that comes from data rather than the
prior (0 = prior only);
* `std`: its standard error, using a running estimate of the unexplained noise;
* `samples`: how many accepted samples actually exercised it;
* `identified`: at least 30 exercising samples and confidence ≥ 0.8.
A coefficient can move without being identified. Example from the tests: two rooms
whose temperature difference stays fairly steady cannot separate exchange between
them from each room's bias; the learner finds a positive coupling but correctly
reports it as not identified.
## Learning conditions
A zone learns from the interval between two polls only when:
* the polls are 4.5–5.5 minutes apart, the relay held one state throughout and the
radiator-lag estimate is known within 0.1 (for example ~32 minutes after an HA
restart);
* the outdoor source did not change and the zone used the same sensors at both
polls;
* for the extended layer, every source in the zone is settled and every adjacent
zone was usable;
* for the ventilation layer, every window state in the zone is known.
No experiments are run and the boiler is never switched to gather data: everything
is learned passively.
## Forecasts
Forecasts simulate all zones together, step by step, over the MPC horizon (60–180
minutes):
* **Weather:** held at current values.
* **Electrical heat:** the variable part fades towards baseline with a configurable
half-life (default 30 minutes; 0 = stops now), and the room keeps following it with
its response time. A gaming PC drawing 600 W now is not assumed to run on for two
hours.
* **Windows:** an open window is assumed to stay open for a configurable time
(default 15 minutes), then close; the zone then recovers.
* **Relay:** the candidate plan being evaluated.
For the plan search the step is compiled into exact per-zone coefficients (every
term is linear in the temperatures and the lag), which keeps the 180-minute search
fast on a Raspberry Pi.
Plan forecasts are **counterfactual** while Generic Thermostat controls the relay:
they describe what would happen under the MPC's proposed plan.
## Validation
The Forecast Error sensors score forecasts that are valid for comparison with
measured temperatures. At every poll the model parameters are frozen; 15, 30, 60
and 120 minutes later all zones are replayed from that poll using the relay,
electrical heat and window history that actually followed (outdoor temperature held
at its start value), and compared with the readings. The base layer and a
no-change forecast are scored on exactly the same spans:
* `mae`, `bias`: the full model's error;
* `persistence_mae`, `skill`: against assuming no change;
* `base_model_mae`, `improvement_vs_base`: against the base layer alone. A feature
that does not improve this should be switched off (for example the gust term).
Results on synthetic apartments (the tests; these check the method, not real-world
accuracy):
| Scenario | 60-min error, full | base | no change |
|---|---|---|---|
| Office, UPS 200 W + 400 W gaming sessions, thermostat cycling | 0.031 °C | 0.182 °C | 0.40 °C |
| Bedroom, 15–20 min ventilation every 4 h, wind and recovery | 0.026 °C | 0.218 °C | 0.52 °C |
| Two adjacent rooms, true exchange 0.01 | 0.024 °C | 0.037 °C | 0.29 °C |
In the ventilation scenario, the same data without the window configured produced
a −0.013 °C/5 min cooling bias and an 11 % inflated boiler coefficient, which is
the contamination the separate ventilation layer prevents.
## Limitations
* One temperature per zone: walls and air are not separate states. The recovery
term approximates the air warming back after ventilation.
* Response times (electrical heat, recovery) are configured, not learned. Compare
settings with `improvement_vs_base`.
* Coupling between zones heated by one boiler is weakly identifiable; it is shrunk
towards 0 and usually reported as not identified.
* Natural and wind ventilation terms both scale with the opening; with little wind
variation their split is uncertain even when their combined effect is accurate.
* Forecasts hold weather constant and use one scenario for electrical heat and
windows; no forecast uncertainty band is computed yet.
* Window sensors with a permanently unknown state keep their zone out of learning;
disable such a window.