Heating MPC thermal model

This document describes the model used from version 0.4.0: what it computes, the units and meaning of every coefficient, when each part learns, what the forecasts assume, and how the model is validated. It is observational: nothing here controls the boiler.

Time step and inputs

The model works in 5-minute steps, the polling interval. For each zone i, each poll provides:

Symbol Meaning Unit Source
T_i Zone temperature: sensor-weighted mean of its usable sensors °C zone sensors
T_out Outdoor temperature (first fresh, valid source) °C weather sources
lag Radiator-lag proxy, 0 (cold) to 1 (fully warm); 20-minute first-order response to the relay, integrated at the relay's actual switch times – relay state + read-only listener
q_i Electrical heat above baseline after its thermal response kW heat sources
O_i Sum of open windows' opening factors, weighted by the share of the interval they were open – window sensors
F_i Same, each window also weighted by cos(angle between wind direction and the window's facing) – windows + wind direction
v, g Wind speed and gust speed m/s weather sources
R_i Recovery weight after the zone's last window closed: exp(−t / τ_rec), 0 below 0.05 – window sensors
T_ref,i Zone temperature at the poll before the window opened °C zone sensors

Equations

Per 5-minute step, the predicted change of zone i is the sum of layers:

ΔT_i = loss    × (T_out − T_i)        envelope heat loss
     + heat    × lag                  boiler, through the radiators
     + bias                           constant gains and losses
     + internal × q_i                 electrical heat above baseline     (extended layer)
     + Σ_j couple:j × (T_j − T_i)     exchange with adjacent zones       (extended layer)
     + vent_natural  × O_i (T_out − T_i)                                 (ventilation layer)
     + vent_wind     × O_i v (T_out − T_i)
     + vent_wind_dir × F_i v (T_out − T_i)
     + vent_gust     × O_i max(0, g − v) (T_out − T_i)                   (optional)
     + vent_cross    × O_i O_other (T_out − T_i)                         (optional)
     + recovery      × R_i (T_ref,i − T_i)

All coefficients are in °C per 5 minutes per unit of their term. They are statistical estimates, not measured physical properties: heat is not boiler efficiency, and a relay that is on does not prove the burner is firing.

In conceptual continuous-time form this corresponds to

C_i dT_i/dt = UA_i (T_out − T_i) + Q_boiler + Q_internal + Q_ventilation + Σ_j K_ij (T_j − T_i) + Q_other

divided through by the zone's effective heat capacity C_i and discretized to 5 minutes. The model is first-order (one temperature per zone). Thermal inertia enters through the radiator lag, the electrical response filter and the recovery term; a separate wall-mass state is not modeled (see Limitations).

Base layer

The base layer is the 3-parameter model of earlier versions (loss, heat, bias), learned per zone. It is always kept: it is the fallback whenever another layer's inputs are unknown, and the comparison that shows whether the other layers help.

Extended layer

Present when a zone has an enabled heat source or an adjacent zone. It learns all base terms plus internal and couple:<zone> and replaces the base layer in forecasts once it is as trained as the base layer needs to be (200 samples, 30 with the relay on, 30 off). If any of its inputs is unknown, the base layer is used.

Electrical heat

For each enabled source:

effective power  = measured W − measured W of enabled sources included in it   (≥ 0)
baseline         = 20th percentile of the last 24 h of effective power, or the manual value
variable heat    = heat fraction × (effective power − baseline) / 1000          (kW)
thermal response : r ← r + (1 − exp(−5 min / τ)) × (variable heat held during the interval − r)

q_i is the sum of the responses of the zone's sources. Centring on the baseline matters: the persistent load (for example a UPS drawing 200 W all day) is already part of the bias term, so feeding it again would count it twice. The baseline needs one hour of data; after startup or an outage a source's response must run for two time constants before it is used for learning.

Only active power counts (W, kW, mW). VA (apparent power) and % (UPS load) are rejected. A UPS output sensor does not include the UPS's own losses; if they matter, measure the input side or lower the heat fraction accordingly.

Ventilation layer

Present when a zone has an enabled window. Learned separately, from the part of the measured change the closed-window layers cannot explain, only while a window is open or the zone is recovering, and only while every window state in the zone is known. While a window is open, possibly open (its sensor is unknown and it was last seen open) or the zone is recovering, the base and extended layers do not learn, so window events cannot inflate loss or shift bias.

An unknown window state is never read as closed, and an opening or closing counts as confirmed only when it was seen: the previous reading was the other state with no unknown period (or restart) in between. If a window closes while its sensor was unknown, the event's duration is reported as a range and the recovery term is not learned from it, because the closing time is not known. Last known states, open events and recovery are saved and restored across restarts, as unknown until the sensor reports again.

An input that a term needs is never filled in for learning or for Model Error: while a window is open, the wind, its direction (for vent_wind_dir) and the other zones' windows (for vent_cross) must be known. With every window closed, the opening terms are 0 and need no weather. Forecasts, which must produce a number, assume calm air for a missing wind input.

vent_wind_dir is bounded by vent_wind (|vent_wind_dir| ≤ vent_wind), so the combined wind term never goes negative: a leeward window still ventilates.

Wind direction is meteorological: the direction the wind comes from, degrees clockwise from north. A window's azimuth is the direction its outside faces. Wind from the azimuth blows straight at the window (cos = 1); wind from behind the building gives −1. Angle differences wrap around north correctly.

Priors, bounds and confidence

Coefficient Prior Bounds Prior worth
loss 0.002 0 … 0.04 as in earlier versions
heat 0.045 0 … 0.25 as in earlier versions
bias 0 −0.06 … 0.06 as in earlier versions
internal 0 0 … 0.5 20 samples at 0.4 kW
couple:j 0 0 … 0.05 200 samples at 1 °C difference
vent_natural 0 0 … 0.2 20 samples at opening 1, 15 °C difference
vent_wind, vent_wind_dir 0 0 … 0.03 / ±vent_wind 20 samples at 4 m/s
vent_gust 0 0 … 0.03 20 samples
vent_cross 0 0 … 0.1 100 samples
recovery 0 0 … 0.5 20 samples at 0.5 °C deficit

New effects start at 0: no effect is assumed until the data shows one. Learning is recursive least squares with exponential forgetting (about 3.5 days of samples), a covariance bound that stops windup during long periods without excitation, and outlier rejection above 0.8 °C per 5 minutes.

Each coefficient reports:

  • confidence: the share of its information that comes from data rather than the prior (0 = prior only), from its posterior variance. It is not a sample count: it grows only while the data varies the coefficient's input independently of the others, and with forgetting it falls again during long periods without such variation. The base layer reports it too (loss, heat, bias);
  • std: its standard error, using a running estimate of the unexplained noise;
  • samples: how many accepted samples actually exercised it;
  • identified: at least 30 exercising samples and confidence ≥ 0.8.

The base layer has no per-coefficient sample counts or standard errors; its confidence alone shows identification. In the tests, two weeks of samples with the relay always off and a steady indoor-outdoor difference leave heat at 0 and loss and bias below 0.8, while four days with the relay cycling and the weather changing bring all three above 0.8.

A coefficient can move without being identified. Example from the tests: two rooms whose temperature difference stays fairly steady cannot separate exchange between them from each room's bias; the learner finds a positive coupling but correctly reports it as not identified.

Learning conditions

A zone learns from the interval between two polls only when:

  • the polls are 4.5–5.5 minutes apart, the relay held one state throughout and the radiator-lag estimate is known within 0.1 (for example ~32 minutes after an HA restart);
  • the outdoor source did not change and the zone used the same sensors at both polls;
  • for the extended layer, every source in the zone is settled and every adjacent zone was usable;
  • for the ventilation layer, every window state in the zone is known.

No experiments are run and the boiler is never switched to gather data: everything is learned passively.

Configuration changes

Every learned component stores a fingerprint of the configuration it was learned under (custom_components/heating_mpc/compatibility.py). At startup, components whose fingerprint changed are reset; the rest are kept.

Change Effect
A zone's sensors, or the ratio of their weights Zone recalibrated: coefficients kept as a starting point; uncertainty, counts and accuracy statistics reset. Its extended and ventilation layers start over too (their loss, heat and bias values kept as a starting point)
Scaling all of a zone's weights equally Nothing (the normalized measurement is unchanged)
A heat source's sensor, heat share, baseline, response time or "included in" internal of its zone; the source's baseline samples if its effective power changed
A neighbour's sensors or weights couple:<neighbour>
A window's sensor, polarity or opening factor that zone's ventilation terms; vent_cross of the other zones
A window's facing direction vent_wind_dir
Recovery time constant recovery
Comfort weight, target offset, names Nothing (not physical)

Models saved before fingerprints existed (0.4.0) are assumed to match the configuration they are loaded with, and are fingerprinted at once. Every reset is logged in model_changes with its reason.

Forecasts

Forecasts simulate all zones together, step by step, over the MPC horizon (60–180 minutes):

  • Weather: held at current values.
  • Electrical heat: the variable part fades towards baseline with a configurable half-life (default 30 minutes; 0 = stops now), and the room keeps following it with its response time. A gaming PC drawing 600 W now is not assumed to run on for two hours.
  • Windows: an open window is assumed to stay open for a configurable time (default 15 minutes), then close; the zone then recovers. A window whose sensor is unknown but was last seen open is assumed open only until that time after it was last seen, never renewed. One last seen closed, or never seen since setup, is assumed closed, and the forecast is flagged as uncertain (uncertain_windows).
  • Relay: the candidate plan being evaluated.

For the plan search the step is compiled into exact per-zone coefficients (every term is linear in the temperatures and the lag), which keeps the 180-minute search fast on a Raspberry Pi.

Plan forecasts are counterfactual while Generic Thermostat controls the relay: they describe what would happen under the MPC's proposed plan.

Validation

Two separate measurements, because they answer different questions.

Model accuracy (Model Error sensors) scores the model, not a forecast. At every poll the model parameters are frozen; 15, 30, 60 and 120 minutes later all zones are replayed from that poll using the relay, electrical heat and window history that actually followed (outdoor temperature held at its start value), and compared with the readings. The base layer and a no-change forecast are scored on exactly the same spans:

  • mae, rmse, bias: the full model's error;
  • persistence_mae, skill: against assuming no change;
  • base_model_mae, improvement_vs_base: against the base layer alone. A feature that does not improve this should be switched off (for example the gust term).

A span counts only if every input the zone's model used was observed at every step (see Ventilation layer; for the extended layer also electrical heat and neighbours, whose own replay must be complete). Otherwise it is counted as incomplete, with the base model's error on it kept apart (incomplete_base_model_mae), since the base model needs only the relay and the outdoor temperature. Spans that cannot be replayed (uncertain radiator lag, no reading at the end) are counted as skipped.

Forecast accuracy (Forecast Error sensor) scores forecasts as published: the start readings, trajectory, plan, model revision and assumptions of the moment they were made, nothing replaced with hindsight. Because the plan is the MPC's proposal while Generic Thermostat controls the relay, a forecast is compared only when the relay followed it. The deviation is the time, up to the horizon, the relay spent in another state than planned, compared block by block from the relay's own switch times; unobserved relay time counts as possible deviation.

Deviation (worst case) Class Used for
≤ 2 min matched Forecast Error figures
≤ 5 min, ≤ 2 min unobserved approximate approximate_stats only
> 5 min observed counterfactual counted, never an error
otherwise incomplete counted, with a reason

Forecasts made with an assumed input (an unknown window or electrical heat) are incomplete as well. The limits follow from the model: d seconds of unplanned boiler heat change a room by about heat × d / 300 with the learned heat coefficient (typically 0.05–0.12 °C per 5 minutes), so 2 minutes stay below half a 0.1 °C sensor step and 5 minutes are about one step.

Both report how much evidence there is. Forecasts start every 5 minutes, so at horizon h consecutive forecasts share most of their span, and all zones share one boiler: effective_samples = samples × 5 / h / zones. Below 5 the quality is insufficient and the sensor's state stays unknown; below 30 it is indicative.

Results on synthetic apartments (the tests; these check the method, not real-world accuracy):

Scenario 60-min error, full base no change
Office, UPS 200 W + 400 W gaming sessions, thermostat cycling 0.031 °C 0.182 °C 0.40 °C
Bedroom, 15–20 min ventilation every 4 h, wind and recovery 0.026 °C 0.218 °C 0.52 °C
Two adjacent rooms, true exchange 0.01 0.024 °C 0.037 °C 0.29 °C

In the ventilation scenario, the same data without the window configured produced a −0.013 °C/5 min cooling bias and an 11 % inflated boiler coefficient, which is the contamination the separate ventilation layer prevents.

Limitations

  • One temperature per zone: walls and air are not separate states. The recovery term approximates the air warming back after ventilation.
  • Response times (electrical heat, recovery) are configured, not learned. Compare settings with improvement_vs_base.
  • Coupling between zones heated by one boiler is weakly identifiable; it is shrunk towards 0 and usually reported as not identified.
  • Natural and wind ventilation terms both scale with the opening; with little wind variation their split is uncertain even when their combined effect is accurate.
  • Forecasts hold weather constant and use one scenario for electrical heat and windows; no forecast uncertainty band is computed yet.
  • Window sensors with a permanently unknown state keep their zone out of learning and its Model Error spans incomplete; disable such a window.
  • A window that is unknown and was last seen closed (or never seen) is assumed closed in forecasts, flagged as uncertain; no open/closed scenario pair is computed.