@@ -31,7 +31,7 @@ This project targets Home Assistant OS on a Raspberry Pi 5, with one existing ON
Choose multiple sensors for a single variable, e.g. OpenWeatherMap then another provider, in priority order. Switch order in **Configure** to run A/B comparisons on successive days, or simply let the second sensor act as fallback. The active source and all current alternative readings are visible in the **Heating MPC Status** entity attributes (`weather`, `weather_active_sources`, `weather_comparison`). The **MPC Outdoor Temperature** sensor also has an `active_source` attribute and an `alternatives` map.
Measurements are normalized where possible: outdoor temperatures to °C; wind to m/s; pressure to hPa; visibility to meters. Unknown units or values outside plausibility bounds are rejected in favor of the next selected sensor. Clouds and humidity are expected in %, rain/snow in mm or mm/h as represented by their upstream sensor. A fallback source may have a different sampling delay; no stale-data age policy exists yet.
Measurements are normalized where possible: outdoor temperatures to °C; wind to m/s; pressure to hPa; visibility to meters. Unknown units or values outside plausibility bounds are rejected in favor of the next selected sensor. Clouds and humidity are expected in %, rain/snow in mm or mm/h as represented by their upstream sensor. A fallback source may have a different sampling delay; configurable report-age limits now reject stale inputs (see below).
Switching only the **weather-provider sensors** does not reset learned thermal parameters. The update is applied after the integration reloads, and it skips learning one transition when the primary temperature source changes, avoiding a jump in the training series. Nevertheless, two sensors with a persistent offset can bias predictions; compare their readings and validate the model again before relying on them. Replacing the physical heating switch discards incompatible model parameters. Existing room-specific parameters are retained if room entity IDs remain unchanged.
@@ -95,6 +95,34 @@ No active control was added; the manifest version has not been advanced.
Predictions remain **counterfactual**: the proposed plan is not the actual
Generic Thermostat's future command sequence.
Offline lifecycle tests use HA doubles. Freshness policies, actual HA/HAOS lifecycle
Offline lifecycle tests use HA doubles. Actual HA/HAOS lifecycle
validation and held-out prediction accuracy remain unfinished. Back up before
trying these changes; follow the safe trial and rollback notes in AUDIT.md.
## Unreleased: sensor freshness
Room and weather report-age limits are available during setup and in Options
(5–1440 minutes). Defaults are 30 minutes for rooms and 120 minutes for weather;
existing entries use these defaults until changed. Celsius/Fahrenheit handling,
compatible learned models and entity IDs are unchanged.
Stale room readings or an absence of fresh outdoor temperature sources pause
learning and predictions. Weather selection skips stale sources; optional weather
outages do not block predictions. Recovery begins a new sampling interval, so no
training spans an outage. Status attribute `input_quality` lists each room and each
weather source by metric, with report age in seconds and a reason: `valid`,
`missing`, `unknown`, `unavailable`, `stale`, `invalid_timestamp`,
`future_timestamp` or `invalid_value_or_unit`.
Freshness uses HA `last_reported`, falling back to `last_updated` only on older HA
versions without that field. It measures HA state reports, not the age of the
original physical measurement: a provider republishing cached data can look fresh.
Some integrations report only changed values; choose limits appropriate to their
reporting behavior. The relay and thermostat are event-driven references and do
not receive these numeric-sensor age limits. Sensor alignment and relay event
history remain future work. These checks run on the existing five-minute poll.
After backing up and upgrading, check report ages in Status, adjust limits in
Options to match your sensors, and verify fallback/recovery with an unavailable
source. Generic Thermostat remains the sole controller. No HAOS trial was performed.